Places where air required for cooling of heating source (surface of engine, vent pipe, generator, main body and other equipment) and engine combustion can be sufficiently circulated
Places convenient for taking out, taking in, operation and maintenance of device.
Places where increase in indoor temperature can be suppressed with installation as close to exhaust gas outlet as possible
Places where fueling, supply and piping of cooling water are convenient
Places where wiring of operating line of generator operation panel and load line area easy and close
Places where there is no resonance due to engine noise or vibration and without influence from surrounding (See standards related to noise and vibration of Environmental Office)
B. Size of Dynamo-Room
Interval between generator and wall: 800 ~ 1000mmm
Length to width ratio of geometrical generator: 1 : 1.5 ~ 2.0
height : 4 ~ 5m (in consideration of vent pipe and chain block device)
Foundation (PAD)
① Should endure dynamic load of generator (gross weight during operation, under 1.5 times of static load).
② Length to width ratio should be at least 30cm bigger than the length and width of generator.